Product Data Sheet   5256

HBL5256

Nickel plated brass flange, brown phenolic (mounting screws packed separately).

Hubbell Wiring Device-Kellems Product Specifications
 Device Type  Flanged Receptacle
 Standard  NEMA
 Amperage  15A
 Voltage  125V
 Poles and Wires  2 Pole, 3 Wire Grounding
 Wiring Method  Side Wire Only
 Hospital Grade ?  No
 Receptacle Grade  Heavy Duty Spec Grade
 Face Style  Finder Groove
 Flange Style  Standard Metallic
 Color  
 NEMA No.  5-15R
 Horsepower  0.5
 Description  Heavy Duty Straight Blade Flanged Receptacle
 Type  2 Pole, 3 Wire, Grounding
 Rating  15A, 125V
 Certification  UL Listed, File E2186, Meets NEMA WD-6 requirements Listed to UL Standard 498, Certified to CSA, C22.2, No. 42
 Terminal Screw Material  #8-32 Brass, Multiple Drive
 Ground Screw Material  #8-32 Brass, Multiple Drive (Green)
 Top Material  Phenolic
 Base Material  Phenolic
 Power Contacts Material  .031" (.8) Phosphor Bronze
 Mounting Screw Material  Brass-Nickel Plated
 Dielectric Voltage  Withstands 2,000V minimum.
 Current Interrupting  Certified for current interrupting at full rated current.
 Temperature Rise  Max 30C temperature rise at full rated current after 50 cycles of overload at 150% of rated current at a power factor of 75%..
 Terminal Identification  Terminals identified in accordance with UL498 (Brass, White, Green).
 Terminal Accommodation  #14-#10 AWG copper stranded or solid conductor only.
 Product Identification  Ratings are a permanent part of the device.
 Flammability  UL 94 V2.
 Operating Temperatures  Maximum continuous 75C, minimum -40C (w/o impact).




 

Hubbell Wiring Device-Kellems