Product Specifications |
Product Type |
Receptacle. |
Device Type |
Single Flush. |
Device Grade |
Hospital. |
Amperage |
15A |
Voltage |
125V |
Poles and Wires |
2 Pole, 3 Wire. |
Wiring Style |
Back & Side. |
Color |
Gray |
NEMA # |
5/15/2003 |
Face |
Nylon. |
Base |
Nylon. |
Line Contacts |
High Performance Brass. |
Clamp Nut |
Steel. |
Mounting Yoke |
Steel, Nickel and Brass Plated
.050" (1.3). |
Terminal Screws |
Combination Brass #10-32. |
Grounding Screw. |
Combination Brass (Green) #8-32.
|
Grounding Clamp Nut |
Brass. |
Circuit ID |
Hot Stamp. |
Auto Ground Clip |
High Performance Brass. |
Mounting Screws |
Combination Steel Zinc-Plated.
|
Dielectric Voltage |
Withstands 2000V per UL498.
|
Maximum Working Voltage |
250V AC or DC |
Current Interrupting |
Certified for current interrupting
at full rated current. |
Temperature Rise |
Less than 30 deg C temperature
rise at full rated current after 50 cycles overload at 150% rated
current for either AC or DC applications per UL498. |
Terminal Identification |
Brass-Hot; Green-Grounding;
Silver-Neutral. |
Terminal Accommodation |
#14-#10 AWG Copper Conductor
Only. |
Product Identification |
Ratings are a permanent part
of the device. |
Flammilibility |
UL 94 V2. |
Operating Temperature |
Maximum Continuous 60 deg C,
Minimum -40 deg C (w/o impact). |
UL Standard |
UL Listed, File #E2258- Guide
#RTRT. |
CSA Standard |
Cetrified to CSA Standard C22.2
No. 42M1984 (General Use Receptacles). |
UL Listing |
UL Listed, File #E2258- Guide
#RTRT. |
Federal Specification |
Federal Specification WC596
(where applicable). |
Complies with: |
NEMA Standards WD-1, WD-6.
|
Overseas Approval |
NOM, CE. |