Product Data Sheet    hgf 8300

HGF8300



Circuit Guard®, Commercial Hospital Grade, Ground Fault Circuit Interrupter, Duplex Receptacle

Hubbell Wiring Device-Kellems Product Specifications
 Hospital Product Type  
 Hospital Grade Receptacle Type  Duplex
 Duplex Receptacle Type  Commercial GFCI
 Amperage  20A
 Voltage  125V
 Color  
 NEMA Number  5-20R
 Horsepower  1
 Description  Hospital Grade Straight Blade Duplex GFCI Receptacle
 Type  2 Pole, 3 Wire, Grounding
 Certification  UL Listed File E41978 Listed to UL Standards 498 for Receptacles 943 Class A GFCI's Certified to CSA File LR2488
 Top Material  Nylon
 Base Material  Nylon
 Power Contacts Material  .03" (.8) Brass
 Ground Contacts Material  .032" (.8) Brass Alloy
 Mounting Strap Material  .05" (1.3) Steel-Zinc Plated
 Terminal Screw Material  #8-32UNC Brass
 Ground Screw Material  #8-32UNC Brass
 Mounting Screws Material  #6-32UNC Steel
 Test/Reset Buttons Material  Nylon
 Dielectric Voltage  Withstands 1500V minimum
 Trip Level  4 to 6 mA
 Trip Time  .025 Sec. Nominal
 Frequency  60 Hz
 Response Time  .025 Sec.
 Maximum Interrupting Capacity  2000A
 Current Interrupting  Certified for current interrupting at full rated current.
 Temperature Rise  Max 30°C temperature rise at full rated current after 50 cycles of overload at 150% of rated current with direct current.
 Terminal Identification  Terminals identified in accordance with UL 498 (Brass, White, Green).
 Terminal Accommodation  #14-#10 AWG copper conductor only.
 Product Identification  Ratings are a permanent part of the device.
 Flammability  94-V2
 Operating Temperatures  -35°C to +66°C (-30°F to +150°F)
 Storage Temperature  -30 to 66 degrees C
 Maximum Humidity  0.95




 

Hubbell Wiring Device-Kellems