| Hubbell Wiring Device-Kellems Product
Specifications |
| Device Type |
Flanged Inlets |
| Standard |
IEC 320 |
| Locking |
No |
| Amperage |
20A/16A |
| Voltage |
250V |
| Poles and Wires |
2 Pole, 3 Wire Grounding |
| Wiring Method |
Back Wired |
| Hospital Grade ? |
No |
| Receptacle Grade |
Heavy Duty Spec Grade |
| Color |
|
| Description |
IEC Straight blade panel mount
power inlet. |
| Type |
2-pole + earth. |
| Rating |
16A 250V AC for European
service; 20A 250V AC for North American service. |
| Certification |
UL Listed 20A 250V AC-File No.
E1706; CSA certified 20A 250V AC-File No. 17337; UL classified to
IEC 320, 16A 250V AC-File No. E111246; TUV and VDE certified at 16A
250V AC-File No. 12469 1550 1002. |
| Contact Blades Material |
.040" (1.0) Brass |
| Ground Contact Blade
Material |
.040" (1.0) Brass |
| Terminal Screw Material |
#6-32 Steel plated |
| Ground Screw Material |
#6-32 Steel plated Multi-drive
|
| Wire Clamps Material |
.062 (1.8) Steel-nickel finish
|
| Base Material |
Impact Modified PBT |
| Dielectric Voltage |
Withstands 2,000V minimum.
|
| Current Interrupting |
Certified for current
interrupting at full rated current. |
| Temperature Rise |
Max 30°C temperature rise at
full rated current after 50 cycles of overload at 150% of rated
current at a power factor of 75%.. |
| Terminal Identification |
Terminals identified in
accordance with UL498 (Brass, White, Green). |
| Terminal Accommodation |
North American-#16AWG-#12AWG;
International-1.5mm²-2.5mm². |
| Product Identification |
Ratings are a permanent part of
the device. |
| Flammability |
UL 94 V2. |
| Operating Temperatures |
Maximum continuous 75°C,